10KV Single Core Heat Shrinkable Straight Joint
Type & Specification | |||||||
Name | Item No. | Suit cables' sectional area (m㎡) | Name | Item No. | Suit cables' sectional area (m㎡) | ||
10KV Single Core Heat Shrinkable Indoor Termination Kits | VRSN-10/1.1 | 25~50 | 10KV 3-cores Heat Shrinkable Indoor Termination Kits | VRSN-10/3.1 | 25~50 | ||
VRSN-10/1.2 | 70~120 | VRSN-10/3.2 | 70~120 | ||||
VRSN-10/1.3 | 150~240 | VRSN-10/3.3 | 150~240 | ||||
VRSN-10/1.4 | 300~400 | VRSN-10/3.4 | 300~400 | ||||
VRSN-10/1.5 | 500~630 | VRSN-10/3.5 | 500~630 | ||||
10KV Single Core Heat Shrinkable Outdoor Termination Kits | VRSW-10/1.1 | 25~50 | 10KV 3-cores Heat Shrinkable Outdoor Termination Kits | VRSW-10/3.1 | 25~50 | ||
VRSW-10/1.2 | 70~120 | VRSW-10/3.2 | 70~120 | ||||
VRSW-10/1.3 | 150~240 | VRSW-10/3.3 | 150~240 | ||||
VRSW-10/1.4 | 300~400 | VRSW-10/3.4 | 300~400 | ||||
VRSN-10/1.5 | 500~630 | VRSN-10/3.5 | 500~630 | ||||
10KV Single Core Heat Shrinkable Joint | VRSJ-10/1.1 | 25~50 | 10KV 3-cores Heat Shrinkable Joint | VRSJ-10/3.1 | 25~50 | ||
VRSJ-10/1.2 | 70~120 | VRSJ-10/3.2 | 70~120 | ||||
VRSJ-10/1.3 | 150~240 | VRSJ-10/3.3 | 150~240 | ||||
VRSJ-10/1.4 | 300~400 | VRSJ-10/3.4 | 300~400 | ||||
VRSN-10/1.5 | 500~630 | VRSN-10/3.5 | 500~630 |
Tech Data | |||||
Test Project | Standard Requirements | Test Result/Conclusion | |||
1min Power Frequency Voltage (wet state) | 45KV, No breakdown no flashover | No flashover and breakdown of the combined sample under 45KV, 1min wet state | |||
Partial discharge test 13KV devolution power not more than 20PC | 13KV≤20PC | A, B, C three-phase discharge capacity is 2pc under 13KV | |||
Heating Cycles Voltage Test | Conductor heating to 90-95 ℃, each cycle for 8h, including heating 5h, cooling 3h, a total of three cycles | Complete three load cycle tests as required by the standard | |||
Impulse Voltage Test | 105KV positive and negative polarity 10 times each, no flashover and breakdown of the combined specimen | 105KV positive and negative polarity 10 times each, no flashover and breakdown | |||
Negative Polarity DC Voltage Test | 52KV, No breakdown no flashover | 52KV, 15min, No flashover and breakdown of combined specimens | |||
4H Power Frequency Voltage Test | 35KV, No breakdown no flashover | 35KV, 4h, No flashover and breakdown of combined specimens |
Production Ability• 8 professional production lines • 7900 square meters of workshop area • dozens of cable accessories production equipment | |
R&D Capabilities • many years of experience in R&D and customization of cable accessories, Professional R&D team • a number of professional technical engineers • mature professional technologies such as conductor link and electric field control. • Passed and obtained a number of qualification certifications | |
Honorary Certification • CE and SGS certification reports underwritten by PICC • High-tech Enterprise • Jiangsu cable accessories industry (top ten) • Jiangsu energy saving and environmental protection products |
Provide reasonable and professional use and matching solutions according to customer needs. After signing the contract, a special person will be responsible for process follow-up, timely control the progress, and cooperate with logistics to ensure the smooth delivery of the order. Perfect after-sales guarantee system, 30-year warranty, manuals and professional installation instructions are provided at the same time |